Journeyman Electrician Exam Cheat Sheet NEC 2026
Free printable reference — eletest.tthefl.com  ·  For study use only · Not a substitute for the NEC codebook

Ohm’s Law & Power Formulas

V = I × R    I = V ÷ R    R = V ÷ I
P = V × I    P = I² × R    P = V² ÷ R

Voltage Drop: VD = (2 × K × L × I) ÷ CM
K = 12.9 (copper), 21.2 (aluminum). L = one-way distance (ft). CM = circular mils.

Three-phase power: P = V × I × 1.732 × PF

Motor Sizing (Art. 430)

  • Branch circuit conductor: FLA × 125%
  • Standard inverse-time breaker: FLA × 250%
  • Overload protection: FLA × 115% (SF ≥ 1.15, temp rise ≤ 40°C) or FLA × 125%
  • Disconnecting means: within sight of motor and controller
  • Three-phase FLA: see Table 430.250

Grounding Electrode Conductor (Art. 250)

Table 250.66 — copper GEC size by service conductor size:

Service ConductorMin. Copper GEC
2 AWG or smaller8 AWG
1 AWG – 1/0 AWG6 AWG
2/0 AWG – 3/0 AWG4 AWG
Over 3/0 AWG – 350 kcmil2 AWG
Over 350 kcmil – 600 kcmil1/0 AWG
Over 600 kcmil – 1100 kcmil2/0 AWG
Over 1100 kcmil3/0 AWG

Conductor Ampacity — Copper (Table 310.12)

AWG / kcmil60°C (140°F)75°C (167°F)90°C (194°F)
14 AWG15 A20 A25 A
12 AWG20 A25 A30 A
10 AWG30 A35 A40 A
8 AWG40 A50 A55 A
6 AWG55 A65 A75 A
4 AWG70 A85 A95 A
3 AWG85 A100 A115 A
2 AWG95 A115 A130 A
1 AWG110 A130 A145 A
1/0 AWG125 A150 A170 A
2/0 AWG145 A175 A195 A
3/0 AWG165 A200 A225 A
4/0 AWG195 A230 A260 A

Derating applies for >3 current-carrying conductors, ambient temps ≠ 30°C, or continuous loads.

Dwelling Load Calc — Standard Method (Art. 220)

  1. General lighting: sq ft × 3 VA
  2. Small appliance circuits: 2 × 1,500 VA = 3,000 VA
  3. Laundry circuit: 1,500 VA
  4. Apply demand factor (Table 220.42): first 3,000 VA @ 100%; remainder @ 35%
  5. Add individual loads (dryer, range, A/C, water heater) at nameplate or NEC demand factor
  6. Total VA ÷ 240V = minimum amperes

GFCI Required Locations — NEC 2026 (Art. 210.8)

LocationRequired SinceNotes
BathroomsNEC 1975All receptacles within 6 ft of sink edge
GaragesNEC 1978All 125V, 15/20A receptacles
OutdoorsNEC 1978All 125V, 15/20A receptacles
Crawl spacesNEC 1990All 15/20A receptacles at or below grade
Unfinished basementsNEC 1990All 15/20A receptacles
Kitchen countertopsNEC 1987Receptacles within 6 ft of sink
BoathousesNEC 1990All 15/20A receptacles
Pool areas / hot tubsVariousSee Art. 680 for all receptacle locations
Dishwasher circuitNEC 2020Single-phase 125V branch circuit
Laundry areasNEC 2023All receptacles
Indoor damp/wet locationsNEC 2014All 15/20A receptacles

AFCI Required Locations — NEC 2026 (Art. 210.12)

NEC 2026 Major Expansion: AFCI protection is now required for nearly all 120V, 15A and 20A branch circuits in dwelling units, including circuits serving: bedrooms, kitchens, living rooms, dining rooms, halls, closets, sunrooms, recreation rooms, and similar rooms.

AFCI devices: combination-type AFCI breaker at the panel, or outlet branch circuit AFCI device at the first outlet.

NEC 2026 New Requirements to Know

ArticleNew Requirement
210.12AFCI protection expanded — nearly all 120V dwelling circuits
210.17EV-ready outlet required in garages of new single-family homes
230.67Surge protective device (SPD) required at service equipment for new installations
625EV charging equipment article fully rewritten — covers bidirectional (V2G) charging
706Energy storage systems (home batteries, solar+storage) — significantly expanded requirements

Key NEC Articles for the Journeyman Exam

ArticleTopicWhat to Know
100DefinitionsOCPD, feeder, branch circuit, dwelling unit, accessible, identified
210Branch CircuitsMost-tested article — GFCI, AFCI, ratings, outlet spacing
220Load CalculationsStandard dwelling method — general lighting, appliances, demand factors
230ServicesLocation, sizing, disconnecting means, clearances
240Overcurrent ProtectionBreaker sizing, location, accessibility, standard sizes
250Grounding & BondingGEC sizing (Table 250.66), electrode system, EGC, bonding jumpers
300Wiring Methods — GeneralClearances, protection, conduit fill, underground rules
310ConductorsAmpacity (Table 310.12), insulation types, derate rules
430Motors125% conductor, 250% OCPD, overload, disconnect sizing

Exam Day Tips