HVAC Electrical Theory Quick Reference
Free printable reference — eletest.tthefl.com  ·  For study use only

Ohm’s Law & Power Formulas

V = I × R     I = V ÷ R     R = V ÷ I
P = V × I     P = I² × R     P = V² ÷ R

Where: V = voltage (volts), I = current (amps), R = resistance (ohms), P = power (watts)

Example: A 240V compressor draws 15A → P = 240 × 15 = 3,600 watts = 3.6 kW

Series vs. Parallel Circuits

Series: Same current flows through all. One open = entire circuit dead. Rtotal = R1 + R2 + …

Parallel: Same voltage across all branches. One branch can open without stopping others.
1/Rtotal = 1/R1 + 1/R2 + … (total resistance is always less than the smallest branch)

In HVAC: Control circuits are series. Line voltage loads (compressor, blower, condenser fan) are parallel.

Transformer Basics

Turns ratio: Vprimary / Vsecondary = Nprimary / Nsecondary

Residential control transformer: 240V primary → 24V secondary (common: 40VA, 75VA, 100VA)

Control circuit fuse: Typically 3A fuse on 24V secondary. Blown fuse = no 24V = no thermostat call response.

kVA RatingMax Load at 24V
20 VA0.83 A
40 VA1.67 A
75 VA3.1 A
100 VA4.2 A

Single-Phase Motor Types

TypeFull NameHow It StartsWhere Used
PSCPermanent Split CapacitorRun capacitor only — always in circuitCondenser fans, most blower motors
CSIRCapacitor Start, Induction RunStart capacitor + centrifugal switch, disconnects at ~75% speedSingle-phase compressors, pumps
CSCRCapacitor Start, Capacitor RunStart cap + run cap; start cap removed by switch after startHard-start compressors
ECMElectronically Commutated MotorBrushless DC motor driven by internal inverter — no capacitorVariable-speed blowers (high efficiency)
Shaded PoleShaded PoleShading coil creates phase shift — no capacitorSmall evaporator fans, low-torque loads

Capacitor Testing

Test with a capacitor meter (capacitance function). A capacitor is good if the measured microfarad (MFD/µF) value is within ±6% of the rated value printed on the label.

Rated MFDAcceptable Range (±6%)
5 MFD4.7 – 5.3 MFD
10 MFD9.4 – 10.6 MFD
30 MFD28.2 – 31.8 MFD
45 MFD42.3 – 47.7 MFD

Danger: Discharge capacitors before testing or handling. A charged run capacitor can deliver a dangerous shock even with power off.

Reading a Ladder Diagram (Control Circuit Tracing)

A ladder diagram has two vertical rails (L1 and L2, or R and C for 24V). Each horizontal rung is one control function. Current flows LEFT to RIGHT from the power rail through contacts and loads.

SymbolMeaningState When Coil De-Energized
NO contact (normally open)Open at rest — closes when relay/contactor coil energizesOpen → no current
NC contact (normally closed)Closed at rest — opens when relay/contactor coil energizesClosed → current flows
Coil circleRelay or contactor coil — energizes when rung path is complete
Safety switch (open)Limit switch, pressure switch, or thermostat — interrupts circuitDepends on type

Trace a cooling call: Thermostat Y closes → 24V energizes contactor coil → NO contacts of contactor close → 240V to compressor and condenser fan.

Common HVAC Electrical Faults

SymptomLikely CauseQuick Test
System does not start at allBlown fuse/tripped breaker, failed transformer, open thermostatCheck supply voltage, then 24V at transformer secondary terminals
Compressor hums, will not startBad start or run capacitor, low voltage, locked rotorMeasure capacitor MFD; measure voltage at compressor terminals
Blower runs, compressor does notContactor not pulling in, low-pressure switch open, start delay timerMeasure voltage at contactor coil (should be 24V when Y is closed)
System runs, trips breakerHigh amp draw — bad capacitor, dirty coil, refrigerant overchargeClamp-meter amps at compressor leads vs. nameplate RLA
Control transformer fuse blows repeatedlyShort circuit in 24V control wiring or shorted coilDisconnect each 24V load (contactor, reversing valve, etc.) one at a time until fuse holds
No cooling but blower and compressor runReversing valve stuck (heat pump), low refrigerant, bad TXVCheck supply and return air temps, compressor suction and discharge pressures

HVAC Electrical Code — Key NEC Rules (Art. 440)

RuleWhat It Means
Use nameplate MCA for conductor sizingMCA (Minimum Circuit Ampacity) is on the equipment label — size the branch circuit wire to this value, not just the compressor FLA
Use nameplate MOCP for breaker/fuseMOCP (Maximum Overcurrent Protection) is on the label — never exceed this for the branch circuit OCPD
Disconnect within sightA disconnect switch must be within sight (visible, ≤ 50 ft) of outdoor A/C equipment. Must be lockable in the open position.
Nameplate wins over NEC tablesFor HVAC equipment, follow the nameplate. It already accounts for locked-rotor current and compressor motor characteristics. Art. 440 modifies Art. 430.

Electrical Safety — HVAC Work